Product Detail:
1. Application
JR29 series thermal overload relay is mainly suitable for A.C.electric power system with volt-age up to 660V, current up to 500A, 50/60Hz. It is generally used for the protection of overloadand phase-lacking in circuits with three-phase induce motors and is often made up electromag-netic starters with CJX8 series A.C. contactors. The product conforms to IEC60947-4-1 stardand.Noter: JR29-16 is manually reset automatic to the other.
2. Motion Characteristic: Three-phase Balance Motion Time
| No | Times the setting current | Motion time | Start conidition | Ambient temperature | ||
| 1 | 1.05 | >2h | cold state | 20oC±5oC | ||
| 2 | 1.2 | <2h | heat state (Following the No.1 test) | |||
| 3 | 1.5 | <4min | ||||
| 4 | 7.2 | 10A | 2s< TP ≤ 10S | ≤ 63A | cold state | |
| 10 | 4s< TP ≤ 10S | ≤ 63A | ||||
3. Phase-losing Motion Characteristic
| No | Times the setting current | Motion time | Start condition | Ambient temperature | |
| Any two phase | Another phase | ||||
| 1 | 1.0 | 0.9 | >2h | cold state | 20o>C±5oC |
| 2 | 1.15 | 0 | <2h | heat state (Following the No.1 test) | |
4. Specification
| Type | Setting Range(A) | For Contactor |
| JR29-16 | 0.11~0.16 | CJX8-09 CJX8-16 |
| 0.14~0.21 | ||
| 0.19~0.29 | ||
| 0.27~0.4 | ||
| 0.35~0.52 | ||
| 0.42~0.63 | ||
| 0.55~0.83 | ||
| 0.7~10. | ||
| 0.9~1.3 | ||
| 1.1~1.5 | ||
| 1.3~1.8 | ||
| 1.5~2.1 | ||
| 1.7~2.4 | ||
| 2.1~3 | ||
| 2.7~4 | ||
| 3.4~4.5 | ||
| 4~6 | ||
| 5.2~7.5 | ||
| 6.3~9 | ||
| 7.5~11 | ||
| 9~13 | ||
| 12~17.6 |